100% unbalanced output, max. output up to 50% rated power for each phase

AC couple to retrofit existing solar system

Max. 10 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel

Max. charging/discharging current of 350A

48V low voltage battery, transformer isolation design

6 time periods for battery charging/discharging

Support storing energy from diesel generator

ModelSUN-14K-SG05LP3-EU-SM2SUN-15K-SG05LP3-EU-SM2SUN-16K-SG05LP3-EU-SM2SUN-18K-SG05LP3-EU-SM2SUN-20K-SG05LP3-EU-SM2
Battery Input Data
Battery TypeLead-acid or Lithium-ion
Battery Voltage Range (V)40-60
Max. Charging Current (A)260280300330350
Max. Discharging Current (A)260280300330350
Charging Strategy for Li-ion BatterySelf-adaption to BMS
Number of Battery Input1
PV String Input Data
Max. PV Access Power (W)2800030000320003600040000
Max. PV Input Power (W)2240024000256002880032000
Max. PV Input Voltage (V)800
Start-up Voltage (V)180
MPPT Voltage Range (V)160-650
Rated PV Input Voltage (V)550
Max. Operating PV Input Current (A)36+36
Max. Input Short-Circuit Current (A)54+54
No. of MPPT Trackers/No. of Strings MPP Tracker2/2+2
AC Input/Output Data
Rated AC Input/Output Active Power (W)1400015000160001800020000
Max. AC Input/Output Apparent Power (VA)1540016500176001980022000
Rated AC Input/Output Current (A)21.3/20.322.8/21.824.3/23.227.3/26.130.4/29
Max. AC Input/Output Current (A)23.4/22.425/2426.7/25.630/28.733.4/31.9
Max. Continuous AC Passthrough (grid to load) (A)70
Peak Power (off-grid) (W)2 times of rated power, 10s
Power Factor Adjustment Range0.8 leading to 0.8 lagging
Rated Input/Output Voltage/Range (V)220/380V, 230/400V, 0.85Un-1.1Un
Rated Input/Output Grid Frequency/Range(Hz)50/45-55, 60/55-65
Grid Connection Form3L+N+PE
Total Current Harmonic Distortion THDi<3% (of nominal power)
DC Injection Current<0.5% In
Efficiency
Max. Efficiency97.6%
Euro Efficiency97.0%
MPPT Efficiency>99%
Equipment Protection
IntegratedDC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection
Surge Protection LevelTYPE II(DC), TYPE II(AC)
Interface
Communication InterfaceRS485/RS232/CAN
Monitor ModeGPRS/WIFI/Bluetooth/4G/LAN(optional)
General Data
Operating Temperature Range (°C)-40 to +60°C, >45°C Derating
Permissible Ambient Humidity0-100%
Permissible Altitude2000m
Noise (dB)<30
Ingress Protection (IP) RatingIP 65
Inverter TopologyNon-isolated
Over Voltage CategoryOVC II(DC), OVC III(AC)
Cabinet Size (WxHxD mm)456×750×238.5 (Excluding Connectors and Brackets)
Weight41.9
Type of CoolingIntelligent Air Cooling
Warranty5 Years/10 Years
the Warranty Period Depends the Final Installation Site of Inverter. More Info Please Refer to Warranty Policy
Grid RegulationIEC 61727, IEC 62116, CEI 0-21, S09, NRS-097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105
Safety / EMC StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2

Reviews

There are no reviews yet.

Be the first to review “15 Deye 3 Phase – Low Voltage”

Your email address will not be published. Required fields are marked *